TSI Media System

  • Scalable up to 6 KVA
  • Enhanced Power
  • Conversion Feature
  • Supports redundancy
  • Hot Swappable
  • Input DC Breakers
  • Output AC Breakers
  • Optional NEMA Outlets

Parallelable, rack-mounted inverter systems provide a pure AC sine wave output at 120V or 240Vac, 60 or 50Hz, with a THD <3% for any kind of load. Utilizing 48Vdc input, these high density systems range from 1500VA to 6000VA and are mountable in either a 19in open relay rack or conventional box bays.

The TSI sets the standard for True Redundant Systems:

  • Hot Swappable means of disconnect
  • Distributed Static Transfer Switch (STS) function
  • removes system Single Point of Failure
  • Parallelable for redundancy and increased reliability
  • Automatic load sharing when paralleled
  • System sound handling of internal or load generated short circuits

Unlike traditional inverters, the TSI features an AC-AC conversion that double filters and isolates the AC input. When operated in this “Enhanced Power Conversion” (EPC) mode, your overall efficiency is increased to 94% without compromise to the quality and stability of the output wave form. Unlike hard transfers between energy input sources the TSI “softswitching “method is disturbance free. The TSI delivers pure power to your critical load despite normal disturbances such as harmonics, surges, glitches, voltage fluctuations, etc.. Pure sinusoidal output current delivered even in non-linear load conditions.

Pure sine wave at the output and ideal power factor at the input without drawing any energy from your DC supply source.

Your future power demands are likely to be unknown and unpredictable. You get TOTAL MODULARITY with the TSI since there is no need to size a single static switch for the future power demand of the system. With the TSI you can configure your system as you gradually increase its capacity in line with your increasing load demands. No need to oversize or overspend on your initial purchase.

Compact in size, these inverters enable you to deliver maximum power in limited space. Its massive power density provides up to 3000VA in a 2U package or 6000VA in a 4U. This package includes the space savings of built-in STS function, DC and AC distribution and output PDU. These modules can be configured with standard Nema or Twist Lock receptacles allowing for simple application and installation of the TSI-MEDIA platform systems without any need for additional hardware.

These inverters can be mounted in 19-inch open relay racks or box bays.

MEDIA packages are compatible with standard TSI monitoring devices.

Twin Sine Inverter Technology Twin Sine Inverter Technology
TSI Media System
General Specifications
EMC (immunity)IEC 1000-4
EMC (emission)FCC PART 15
SafetyUL 1778 (Ed.4)
CoolingForced
MTBF>200 000 hrs
Efficiency (MAX) On Line90%
Enhanced Power Conversion (EPC)93%
Dielectric strength DC/AC (@ 0,6mA)4300Vdc
True Redundant SystemsCompliant
3 disconnection levels on ACout and DCin power ports
4 disconnection levels on ACin port / 2 communication bus
RoHS-6Compliant
Connection I/OTerminal block
Or NEMA receptacle Or Twist Locks
Or combo AC output receptacles
Protected against reversed polarity
Self adaptive to wide operating conditions
AC Output Power
Nominal Output powern x 1500 VA
Output power (resistive load)n x 1200W
Short time overload capacity150% 15 second
Permanent overload capacity110% @ 40°C
Load power factorFull power rating from 0 inductive to 0 capacitive
Internal temperature management and cut off
DC Input Specifications
Nominal voltage (DC)48 V
Voltage range (DC)40 - 60 V
Nominal current (at 40Vdc)n x 34 A
Maximum input current (for 5 sec.)n x 42 A
Voltage ripple (resistive load @ 54Vdc)< 1mV
Input voltage boundaries user selectable
AC Input Specifications
Nominal voltage (AC)120V 1P or 2P
Voltage range (AC) (each phase)83 – 140 V
Conformity rangeAdjustable
Power Factor>99%
Frequency range (selectable)50 - 60 Hz
Synchronization range47 – 53 Hz / 57 – 63 Hz
AC Output Specifications
Nominal voltage (AC) (Single or dual phase selectable at order)120V or 240 V
Voltage range (AC) (adjustable)90 – 130 V
Voltage accuracy2 %
Frequency50 – 60 Hz
Frequency accuracy0.03 %
Total harmonic distortion (resistive load)<3 %
Load impact recovery time0.4 ms
Turn on delay30 s
Nominal current (Protected against reverse current)n x 12.5 A
Crest factor at nominal power (With short circuit management and protection)2.2
Short circuit clear up capacity (Available while Mains is available at AC input port; With magnitude control and management)10 x In for 20msec
Transfer Performance
Total transient voltage duration (transient free)0 s
Environment
Altitude above sea<1500m
Ambient temperaturen x 1500VA -20 to 50 °C
Pmax at 100% LOAD
Derating up to 65°C
Storage temperature-40 to 70 °C
Relative humidity95% , non condensing
Signaling and Supervision
DisplaySynoptic LED
Alarms output (optional)Dry contacts on shelf
SupervisionUse optional devices
Comprehensive table of troubleshooting codes
Weight and Dimensions
Width19” or 23” Open relay rack and box bay compatible
Depth12.5-inch - 300 mm
Height1500/3000VA 2 U
Weight7.9 Kg + n x 2.4 Kg
Material (casing)Coated steel
Input (DC)
24V 48V 110V 220V
1500 VA per mod
3000 VA per shelf (max)
X 120V Output
(AC)
X 230V
Document Downloads
Title Type Version Date
CE+T America - Media Inverter Systems Datasheet V06 July 27, 2009
CE+T America Product Guide Datasheet December 1, 2008