ProductsTwin Sine InvertersBravo 3-phase 75 KVA Inverter System
Bravo 3-phase 75 KVA Inverter System
  • Energy Efficient – the Twin Sine Inverter (TSI ) performance is unmatched in the industry
  • Maximum Reliability
  • Up to 10 KVA in one 19 inch 2U rack space
  • Efficiency up to 95%
  • 75KVA 3-phase and 80KVA dual phase in one cabinet with additional U space for rectifiers
  • Hot Swappable 2.5 KVA or 1.5 KVA TSI modules simplify replacement or growth additions
  • Remote Monitoring via SNMP option


CE+T is a solutions provider for the telecommunication, industrial, and data center markets in support of their critical power requirements. Founded in 1936, CE+T is an industry leader in power conversion technology. The announcement of the TSI has revolutionized the inverter market with its new range of modular scalable products to support telecom (24VDC, 48VDC) and industrial (110VDC, 220VDC) applications.

Building your system portfolio to meet your varied power demands requires you to have an easily configurable product architecture. TSI technology makes it simple to size and select your inverter configuration without compromising the performance of your system or your budget.

The TSI inverter is modular and scalable to capacities up to 75KVA 3 phase, 80KVA dual phase and is easily configured to your current and future AC requirements. TSI inverters are available in either 1500VA (Media) or 2500VA (Bravo) building blocks.

The TSI Distributed Static Transfer Switch Technology eliminates the single point of failure in a traditional inverter design. Unlike hard transfers between energy input sources the TSI “soft switching” method is disturbance free.

The TSI inverter is field upgradeable and its hot swappable modular design reduces risks caused by exposing your critical load to an unpredictable AC source. There is no need to go to bypass when adding or changing the capacity of your inverter system.





Twin Sine Inverter Technology Twin Sine Inverter Technology
Bravo 3-phase 75 KVA Inverter System
General Specifications
EMC (immunity)EN 61000-4
EMC (emission)EN 55022 (Class B)
SafetyUL Pending
CoolingForced
IsolationDoubled
Efficiency (Typical)
Enhanced Power Conversion95%
On Line90%
Dielectric strength DC/AC4300Vdc
Connection I/O
Reverse polarity protectionTerminal block
RoHSCompliant
AC Output Power
Nominal Output power (max)75,000 VA
Output power (resistive load)60,000 W
Short time overload capacity150% 5 seconds
Permanent overload capacity110%
Load power factorFull power rating from 0 inductive to 0 capacitive
Internal temperature management
DC Input Specifications
Nominal voltage (DC)48 V
Voltage range (DC)40 -60 V
Nominal current (at 40Vdc)1680 A
Maximum input current (for 5 second)2520 A
Voltage ripple2mV
Input voltage boundariesuser selectable
AC Input Specifications
Nominal voltage (AC)120 V
Voltage range (AC)83 – 140 V
Conformity rangeAdjustable
Power Factor>99%
Frequency range (selectable)50 -60 Hz
Synchronization range47 – 53 Hz
57 – 63 Hz
AC Output Specifications
Nominal voltage (AC)120 V
Voltage range (AC) (Adjustable)90 – 130 V
Voltage accuracy2%
Frequency50 -60 Hz
Frequency accuracy0.03%
Total harmonic distortion<1.5 % (resistive load)
Load impact recovery time0.4 ms
Soft Start time20 s
Nominal current - Protected against reverse current208 A/Phase
Crest factor at nominal power3.5
Short circuit overload capacity10 x In for 20msec
Transfer Performance
Maximum voltage interruption0 s
Total transient voltage duration (max)0 s
Environment
Altitude above sea< 4,900 Ft
Ambient temperature-20 to 50 °C
Storage temperature-40 to 70 °C
Relative humidity95% , non condensing
Signaling and Monitoring
DisplayLED
AlarmsDry contacts
MonitoringVia T2S Controller
Weight and Dimensions
Width24”
Dep24”
Height72" or 84”
WeightApprox. 500 lbs
Document Downloads
Title Type Version Date
Bravo 3-phase 75 KVA Inverter System Datasheet_Eng Datasheet December 1, 2008